Settings - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
11.1.5
Table 200:
SDDRFUF Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OpModeSel
Disabled
V2I2
V0I0
V0I0 OR V2I2
V0I0 AND V2I2
OptimZsNs
3V0PU
1 - 100
3I0PU
1 - 100
3V2PU
1 - 100
3I2PU
1 - 100
OpDVDI
Disabled
Enabled
DVPU
1 - 100
DIPU
1 - 100
VPPU
1 - 100
50P
1 - 100
SealIn
Disabled
Enabled
VSealInPU
1 - 100
IDLDPU
1 - 100
VDLDPU
1 - 100
Table 201:
SDDRFUF Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
Technical manual

Settings

Unit
Step
-
-
-
-
%VB
1
%IB
1
%VB
1
%IB
1
-
-
%VB
1
%IB
1
%VB
1
%IB
1
-
-
%VB
1
%IB
1
%VB
1
Unit
Step
-
1
Secondary system supervision
Default
Description
Enabled
Disable/Enable Operation
V0I0
Operating mode selection
30
Pickup of residual overvoltage element in % of
VBase
10
Pickup of residual undercurrent element in % of
IBase
30
Pickup of negative sequence overvoltage
element in % of VBase
10
Pickup of negative sequence undercurrent
element in % of IBase
Disabled
Operation of change based function Disable/
Enable
60
Pickup of change in phase voltage in % of
VBase
15
Pickup of change in phase current in % of
IBase
70
Pickup of phase voltage in % of VBase
10
Pickup of phase current in % of IBase
Enabled
Seal in functionality Disable/Enable
70
Pickup of seal-in phase voltage in % of VBase
5
Pickup for phase current detection in % of
IBase for dead line detection
60
Pickup for phase voltage detection in % of
VBase for dead line detection
Default
Description
1
Selection of one of the Global Base Value
groups
Section 11
333

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi

Table of Contents