Function Block - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
14.15.3
14.15.4
Technical manual
input signals to the function. In addition, the function generates alarms based on received
information.

Function block

SSIMG (63)
BLOCK
PRESSURE
BLK_ALM
PRES_ALM
PRESSURE
PRES_LO
TEMP
TEMP
PRES_ALM
TEMP_ALM
PRES_LO
TEMP_LO
SET_P_LO
SET_T_LO
RESET_LO
ANSI09000129-1-en.vsd
ANSI09000129 V1 EN
Figure 262:
SSIMG (63) function block
Signals
Inputs PRESSURE and TEMP together with settings PressAlmLimit,
PressLOLimit, TempAlarmLimit and TempLOLimit are not supported in
this release of 650 series.
Table 420:
SSIMG (63) Input signals
Name
Type
BLOCK
BOOLEAN
BLK_ALM
BOOLEAN
PRESSURE
REAL
TEMP
REAL
PRES_ALM
BOOLEAN
PRES_LO
BOOLEAN
SET_P_LO
BOOLEAN
SET_T_LO
BOOLEAN
RESET_LO
BOOLEAN
Default
Description
0
Block of function
0
Block all the alarms
0.0
Pressure input from CB
0.0
Temperature of the insulation medium from CB
0
Pressure alarm signal
0
Pressure lockout signal
0
Set pressure lockout
0
Set temperature lockout
0
Reset pressure and temperature lockout
Section 14
Monitoring
597