Signals - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 13
Logic
13.1.4
13.1.5
Table 294:
SMPPTRC (94) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
tTripMin
0.000 - 60.000
Table 295:
SMPPTRC (94) Group settings (advanced)
Name
Values (Range)
TripLockout
Disabled
Enabled
AutoLock
Disabled
Enabled
13.1.6
468

Signals

Table 292:
SMPPTRC (94) Input signals
Name
Type
BLOCK
BOOLEAN
TRINP_3P
BOOLEAN
SETLKOUT
BOOLEAN
RSTLKOUT
BOOLEAN
Table 293:
SMPPTRC (94) Output signals
Name
Type
TRIP
BOOLEAN
CLLKOUT
BOOLEAN
Settings
Unit
Step
-
-
s
0.001
Unit
Step
-
-
-
-
Operation principle
The duration of a trip output signal from tripping logic common 3-phase output
SMPPTRC (94) is settable (tTripMin). The pulse length should be long enough to secure
the breaker opening.
For three-pole tripping logic common 3-phase output, SMPPTRC (94) has a single input
(TRINP_3P) through which all trip output signals from the protection functions within the
IED, or from external protection functions via one or more of the IEDs binary inputs, are
Default
Description
0
Block of function
0
Trip all phases
0
Input for setting the circuit breaker lockout function
0
Input for resetting the circuit breaker lockout function
Description
Common trip signal
Circuit breaker lockout output (set until reset)
Default
Description
Enabled
Disable/Enable Operation
0.150
Minimum duration of trip output signal
Default
Description
Disabled
On: Activate output (CLLKOUT) and trip latch,
Off: Only output
Disabled
On: Lockout from input (SETLKOUT) and trip,
Off: Only input
1MRK 502 048-UUS A
Technical manual