ABB Relion Technical Manual page 747

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
Technical manual
Table 576:
RI and RD type inverse time characteristics
Function
RI type inverse characteristic
1
=
×
t
td
0.236
-
0.339
I
EQUATION1656 V1 EN
I = I
/I
measured
set
RD type logarithmic inverse characteristic
æ
ö
I
-
×
ç
÷
=
5.8
1.35
In
t
è
ø
td
EQUATION1657 V1 EN
I = I
/I
measured
set
Table 577:
Inverse time characteristics for overvoltage protection
Function
Type A curve:
td
=
t
æ
ö
-
V
VPickup
ç
÷
è
ø
VPickup
EQUATION1661 V1 EN
V = V
measured
Type B curve:
×
td
480
=
t
æ
-
V
VPickup
×
-
ç
32
0.5
è
VPickup
EQUATION1662 V1 EN
Type C curve:
×
td
480
=
t
æ
-
V
VPickup
×
-
ç
32
0.5
è
VPickup
EQUATION1663 V1 EN
Time inverse characteristics
Range or value
td = (0.05-999) in steps of 0.01
td = (0.05-999) in steps of 0.01
Range or value
td = (0.05-1.10) in steps of
0.01
td = (0.05-1.10) in steps of
0.01
2.0
ö
-
÷
0.035
ø
td = (0.05-1.10) in steps of
0.01
3.0
ö
-
÷
0.035
ø
Section 21
Accuracy
Accuracy
±5% +60 ms
741