1MRK 502 048-UUS A
12.2.3.2
Table 219:
SXCBR Non group settings (basic)
Name
Values (Range)
tStartMove
0.000 - 60.000
tIntermediate
0.000 - 60.000
AdaptivePulse
Not adaptive
Adaptive
tOpenPulse
0.000 - 60.000
tClosePulse
0.000 - 60.000
SuppressMidPos
Disabled
Enabled
Technical manual
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
TR_OPEN
BOOLEAN
TR_CLOSE
BOOLEAN
RS_CNT
BOOLEAN
XIN
BOOLEAN
Table 218:
SXCBR Output signals
Name
Type
XPOS
GROUP SIGNAL
EXE_OP
BOOLEAN
EXE_CL
BOOLEAN
OP_BLKD
BOOLEAN
CL_BLKD
BOOLEAN
UPD_BLKD
BOOLEAN
POSITION
INTEGER
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
TR_POS
INTEGER
CNT_VAL
INTEGER
L_CAUSE
INTEGER

Settings

Unit
Step
s
0.001
s
0.001
-
-
s
0.001
s
0.001
-
-
Default
Description
0
Signal for open position of apparatus from I/O
0
Signal for close position of apparatus from I/O
0
Signal for open position of truck from I/O
0
Signal for close position of truck from I/O
0
Resets the operation counter
0
Execution information from CSWI
Description
Group connection to CSWI
Executes the command for open direction
Executes the command for close direction
Indication that the function is blocked for open
commands
Indication that the function is blocked for close
commands
Update of position indication is blocked
Apparatus position indication
Apparatus open position
Apparatus closed position
Truck position indication
Operation counter value
Latest value of the error indication during command
Default
Description
0.100
Supervision time for the apparatus to move
after a command
0.150
Allowed time for intermediate position
Not adaptive
Output resets when a new correct end position
is reached
0.200
Output pulse length for open command
0.200
Output pulse length for close command
Enabled
Mid-position is suppressed during the time
tIntermediate