5.6.2

Connecting to YOKOGAWA PLC (STARDOM)

System Configuration
YOKOGAWA
PLC
Communic
controller
ation Type
Twisted pair cable
*1
STARDOM
Ethernet
(NFCP100,
NFJT100)
*1
When connecting STARDOM to MODBUS
For details, refer to the following manual.
*2
When connect a GOT to a PLC, connect to the PCL Ethernet port via a hub.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standards.
*3
When connecting GT16 to an equipment that meets the 10BASE (-T/2/5) standard, use the switching hub and operate in an
environment where 10Mbps and 100Mbps can be mixed.
*4
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
*5
Use the straight cable.
*6
GT14 models compatible with Ethernet connection are only GT1455-QTBDE, GT1450-QMBDE and GT1450-QLBDE.
PLC Side Setting
Make the communication settings as shown below. For details of the communication settings, refer to the following
manual.
POINT
POINT
POINT
Connection between STARDOM and the PC for communication settings
For the communication settings of STARDOM, STARDOM and the PC for communication settings must be
connected to Ethernet using the Resource Configurator (peripheral software).
5 - 12
5. MODBUS(R)/TCP CONNECTION
5.6 Example of Connection
Connection cable
Connection cable
Max.
*5
Cable model
distance
• 10BASE-T
Shielded twisted
pair cable (STP) or
unshielded twisted
pair cable (UTP):
*4
100m
Category 3, 4, and
5
• 100BASE-TX
Shielded twisted
pair cable (STP):
Category 5 and 5e
YOKOGAWA PLC user's Manual
Peripheral Software Manual for YOKOGAWA PLC
Hub
Connection cable
Connection cable
External
device
*5
Cable model
Twisted pair cable
• 10BASE-T
Shielded twisted
pair cable (STP) or
unshielded twisted
pair cable (UTP):
*2
Hub
Category 3, 4, and
5
• 100BASE-TX
Shielded twisted
pair cable (STP):
Category 5 and 5e
®
/TCP, Modbus Communication Portfolio License is required.
Communication driver
MODBUS/TCP
GOT
*3
GOT
Max.
GOT
Option device
distance
Model
- (Built into GOT)
*4
100m
GT15-J71E71-100
Number of
connectable
equipment
*6
126 GOTs
for 1 PLC