Binary Output And Control Relay Output - GE Multilin F650 Instruction Manual

Hide thumbs Also See for Multilin F650:
Table of Contents

Advertisement

APPENDIX C
Supported Control Relay Output Block fields: Pulse On.
The F650 relay provides 24 DNP Binary/Control Output points. These outputs are mapped to the first 24 commands
configured in the F650. Executing a command is equal to activate the PLC equation that was attached to this command.
Thus all of the 24 DNP Binary/Control Output points are pulsed points. It means that only Pulse On flag will be accepted in
DNP control operations on those points. All commands have configurable names. Changing the command's name can be
done using the F650PC program.
BINARY OUTPUT STATUS POINTS
Object Number: 10
Request Function Codes supported: 1 (read)
Default Variation Reported when variation 0 requested: 2 (Binary Output Status)
CONTROL RELAY OUTPUT BLOCKS
Object Number: 12
Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack)
BINARY/CONTROL OUTPUT POINTS
POINT
NAME/DESCRIPTION
INDEX
0
OPERATION1
1
OPERATION2
2
OPERATION3
3
OPERATION4
4
OPERATION5
5
OPERATION6
6
OPERATION7
7
OPERATION8
8
OPERATION9
9
OPERATION10
10
OPERATION11
11
OPERATION12
GE Multilin
C.1.6 BINARY OUTPUT AND CONTROL RELAY OUTPUT
BINARY/CONTROL OUTPUT POINTS
POINT
INDEX
12
13
OPERATION_00
14
15
16
17
18
19
20
OPERATION_00
21
22
23
F650 Digital Bay Controller
C.1 DNP 3.0 PROTOCOL FOR F650
NAME/DESCRIPTION
OPERATION13
OPERATION14
OPERATION15
OPERATION16
OPERATION17
OPERATION18
OPERATION19
OPERATION20
OPERATION21
OPERATION22
OPERATION23
OPERATION24
C
C-15