9 COMMISSIONING
Set the relay as follows
Apply voltage as indicated on the table under the overvoltage setting level and verify that the relay does not trip.
Verify that the relay trips for the set voltage (with an admissible error of 5%).
ELEMENTS
INPUT
59NH/59NL
VX
This element can also be tested by applying only phase voltages. For this purpose, it is necessary to set Auxiliary Voltage =
VX. In this condition, Vn voltage is calculated as a sum of the phase voltages.
GE Multilin
9.14 OVERVOLTAGE ELEMENTS (59P, 59X, 59NH, 59NL, 47)
GENERAL SETTINGS
Auxiliary Voltage
VN
NEUTRAL OV HIGH/LOW (59NH/59NL)
Function
ENABLED
Pickup Level
120 V
Trip Delay
2.00
Reset Delay
0.00
PICKUP LEVEL
TRIP DELAY
(VOLTS)
(SECONDS)
120
2
F650 Digital Bay Controller

9.14.3 59NH AND 59NL ELEMENTS

APPLIED
TRIPPING TIME (S)
VOLTAGE (V)
THEORETICA
L
114
NO TRIP
132
2
132
2
ADMISSIBLE
NA
[1.9–2.1 ]
[1.9 – 2.1]
9
9-19