C.1 DNP 3.0 PROTOCOL FOR F650
The F650 relay has a configurable Map of DNP Binary Input points. This map can be formed by up to 10 blocks of 16 binary
states that are configured using "Setpoint->Relay Configuration" menu from the F650PC program. The minimum number of
DNP Binary Input points is 16 and the maximum number is 160. Within these 160 DNP points, 128 bits (8 blocks of 16) are
mapped to Control Events (Setpoint->Relay Configuration->Control Events) and 32 bits (2 block of 16) are mapped to
contacts A, B of 16 Switchgears (Setpoint->Relay Configuration->Switchgear). Each Switchgear in F650 is mapped into
two DNP Binary Input points. Lets say the setting Binary Input Block1 has been set the value Switchgear 1-8, it means that
DNP Binary Input point 0 = Switchgear 1Contact A, DNP Binary Input point 1 = Switchgear 1 Contact B, DNP Binary Input
point 2 = Switchgear 2 Contact A, etc.
To each Control Event or Switchgear Contact, the user can assign any of the binary states of the F650 relay. These states
are contact inputs and outputs, virtual outputs, protection element states, PLC states, etc. DNP Points that correspond to
Control Events o Switchgear Contacts that are not configured will have a zero value in the response.
Using the PLC-Editor, through the F650PC program, selecting menu: Setpoint->Logic Configuration, it will be possible to
implement complex logic, more than simple OR and NOT previous functions. To perform this, in the menu: Setpoint->Relay
Configuration->Control Events assign a Virtual Output to selected point, after that, implement wished logic with the PLC-
Editor.

BINARY INPUT POINTS

Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read), 22 (assign class)
C
Static Variation Reported when variation 0 requested: 2 (Binary Input Change with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Default Class for all points: 1
DEFAULT BINARY INPUT POINTS MAP
POINT
NAME/DESCRIPTION
INDEX
0-127
Control Events 1-128
128
Switchgear 1 Contact A
129
Switchgear 1 Contact B
130
Switchgear 2 Contact A
131
Switchgear 2 Contact B
132
Switchgear 3 Contact A
133
Switchgear 3 Contact B
134
Switchgear 4 Contact A
135
Switchgear 4 Contact B
136
Switchgear 5 Contact A
137
Switchgear 5 Contact B
138
Switchgear 6 Contact A
139
Switchgear 6 Contact B
140
Switchgear 7 Contact A
141
Switchgear 7 Contact B
142
Switchgear 8 Contact A
C-10
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
F650 Digital Bay Controller
APPENDIX C
C.1.4 BINARY INPUT POINTS
Switchgear 8 Contact B
Switchgear 9 Contact A
Switchgear 9 Contact B
Switchgear 10 Contact A
Switchgear 10 Contact B
Switchgear 11 Contact A
Switchgear 11 Contact B
Switchgear 12 Contact A
Switchgear 12 Contact B
Switchgear 13 Contact A
Switchgear 13 Contact B
Switchgear 14 Contact A
Switchgear 14 Contact B
Switchgear 15 Contact A
Switchgear 15 Contact B
Switchgear 16 Contact A
Switchgear 16 Contact B