51Ph/51Pl Unit Setpoints - GE Multilin F650 Instruction Manual

Hide thumbs Also See for Multilin F650:
Table of Contents

Advertisement

5 SETPOINTS
Table 5–38: 51PH/51PL UNIT SETPOINTS
SETPOINT > PROTECTION ELEMENTS > PHASE CURRENT >
> PHASE TOC HIGH > PHASE TOC HIGH 1> PHASE TOC HIGH 2 > PHASE TOC HIGH 3
> PHASE TOC LOW > PHASE TOC LOW 1 > PHASE TOC LOW 2 > PHASE TOC LOW 3
SETPOINT DESCRIPTION
Function permission
Input type
Pickup level
Curve shape
Time Dial
Reset type
Voltage Restraint
Snapshot Event generation
If the voltage restraint feature is disabled, the pickup level always remains at the value set in the Pickup Level setpoint.
The snapshot event setpoint enables or disables the snapshot event generation for the phase time overcurrent units.
GE Multilin
NAME
DEFAULT VALUE
Function
DISABLED
Input
PHASOR(DFT)
Pickup Level
1.00
Curve
IEEE Ext Inv
TD Multiplier
1.00
Reset
INSTANTANEOUS
Voltage Restraint
DISABLED
Snapshot Events
ENABLED
F650 Digital Bay Controller
5.4 PROTECTION ELEMENTS
STEP
RANGE
N/A
[DISABLED – ENABLED]
N/A
[PHASOR – RMS]
0.01 A
[0.05 : 160.00]
N/A
[See list of curves]
0.01 s
[0.00 : 900.00]
N/A
[INSTANTANEOUS – LINEAR]
N/A
[DISABLED – ENABLED]
N/A
[DISABLED – ENABLED]
5
5-39