Scaling An Analog Value; Using The Potentiometers Of The 40 And 50 Series - ABB AC 31 Technical Manual

Advant controller 31 40 & 50 series
Hide thumbs Also See for AC 31:
Table of Contents

Advertisement

5.10. Scaling an analog value

ABB Control - AC 31
1SBC 260400 R1001-b
06.99
Programming

5.10.1. Using the potentiometers of the 40 and 50 series

The 40 and 50 series central units each have two potentiometers, which allow the adjustment
of parameters without a programming tool.
The MULDI function block may be used for scaling.
The desired setting range in this example is from 0 to 30 000:
Setting range
30000
y
0
The value y set is such that: y = (30 000 * x) / 150 . The result y is placed in the variable
MW 000.00.
POTENTIOMETER_1
VAL_30000
VAL_150
Value read in the
central unit
150
x
0
*:
Z1*
Z2:
%MW000.00
Z3
A1
Page 5-43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents