4.3. Class error descriptions:
Class 1 error descriptions
Flash EPROM checksum error
Class 2 error descriptions
Defective RAM (user program or
data memory)
Too many simultaneous timers
active on the central unit during
program execution (maximum 42)
Class 3 error descriptions
Unit disconnected
CS 31 bus error (no units
connected to the bus)
Note: If there are only analog units
connected to the CS 31 bus, then
this error could occur when
powering up while the analog units
aren't initialized.
Reason: Analog units have a
lengthy initialization period. They
are recognized thereafter by the
central unit
NCB or NCBR error
Note: one of the CS 31 lines is
defective. Check the red Led status
of the NCB or NCBR to find out
which one is at fault.
Superposed address
Cycle time too short
Page 8-10
Diagnosis
4.3.1. Class 1 error descriptions
Error code in
MW254.00
Dec
Hex
-
-
4.3.2. Class 2 error descriptions
Error code in
MW254.08
Dec
Hex
128
80
D
H
255
FF
D
H
4.3.3. Class 3 error descriptions
Error code in
MW255.00
Dec
Hex
15
0F
D
H
16
10
D
H
17
11
D
H
18
12
D
H
200
C8
D
H
Info 1 in
Info 2 in
MW 254.01
MW 254.02
-
-
Info 1 in
Info 2 in
MW 254.09
MW 254.10
Memory address
-
-
-
Info 1 in
Info 2 in
MW 255.01
MW 255.02
Unit type
Address
-
-
-
-
-
-
Info 3 in
MW 254.03
-
Info 3 in
MW 254.11
-
-
Info 3 in
MW 255.03
-
-
-
-
ABB Control - AC 31
1SBC 260400 R1001-b
06.99