5.2. Binary extensions specifications

Weight
Incorporated binary inputs
- Number of inputs
- Isolation of the inputs/electronic
- Types of inputs
- Input voltage:
Nominal value
Signal at 0 (IEC 1131-2)
Signal at 1 (IEC 1131-2)
- Input current at 24 V d.c.
- Filtering time of an input
- Cable length:
unshielded
shielded
Incorporated outputs
- Number of outputs
- Isolation of the outputs/electronic
- Total charging current, under voltage:
direct 24 V d.c.
resistive load / inrush current
L / R = 20 ms
L / R = 30 ms
L / R = 40 ms
L / R = 60 ms
alternate 24 to 230 V a.c.
- Total charging current
- Output leakage current
- Output waste voltage
- Minimum cut-off value
Page 3-18
Technical specifications
The binary extension units are powered at 5 V by the central unit or extensible remote unit to
which they are connected.
Warning: the extensions must not be connected or disconnected under power supply.
XI 16 E1
220 g
16
1500 V a.c.
PNP
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
4 mA
5 ms
300 m
500 m
-
-
-
-
-
-
-
-
XO 08 R1
XC 08 L1
220 g
220 g
-
8 configurable
-
1500 V a.c.
-
PNP
-
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
-
4 mA
-
5 ms
-
300 m
-
500 m
8 relays
8 transistors
1500 Vrms
1500 V a.c.
1 min
1 min
2 A / 5 A
0.5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
-
0.5 A AC-15
8 x 2 A
8 x 0.5 A
< 200 µA
0.5 V à 500 mA
max.
10 mA at
12 V
12 V d.c.
XK 08 F1
XO 16 N1
220 g
220 g
4
-
1500 V a.c.
-
PNP
-
24 V d.c.
-
0 to + 5 V
+ 15 to + 30 V
7 mA
-
5 ms
-
300 m
-
500 m
-
4 relays
16 transistors
1500 Vrms
1500 V a.c.
1 min
1 min
2 A / 5 A
0.5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
-
0.5 A AC-15
4 x 2 A
16 x 0.5 A
< 200 µA
0.5 V à 500 mA
max.
10 mA at
12 V
12 V d.c.
ABB Control - AC 31
1SBC 260400 R1001-b
06.99