...5.10.1 Control Page (Heat/Cool Control)
MrESEt
c 100. 0
c
50. 0
c
Integral
Off
dErIV
OFF
Derivative
Off
APPb
1. 0
CrSOUr
50. 0
ContrL
PAGE
t–bANd
t–bANd
10. 0
OFFHYS
25. 0
5.10.2 Calculating the Crossover Value – Fig. 5.18
The crossover value is calculated from the expression:
Crossover Value =
Gh/Gc + 1
Where Gh/Gc is the ratio of the two output driver gains.
The most common method for determining the Gh/Gc term is by
using 'nameplate' values from the heat/cool device(s).
If a heat/cool application can produce a maximum of 1.5kW and
absorb 0.75kW:
Output Gain Ratio =
100
Crossover Value =
2 + 1
Manual Reset (cool output)
Set the required proportional band offset, between 0.0 and 100.0% of the
0. 0
engineering range span in 0.1% increments.
999. 0
Derivative Action Time
0. 1
OFF
Set the required time between 0.1 and 999.9 in 0.1 second increments (999.9
seconds = 16.67 minutes). '
Approach Band
3. 0
Set the required value between 0.1 and 3.0 in 0.1 increments. (Set 1.0 initially).
0. 1
Crossover Output Value
100. 0
Set the required value between 0.0 and 100.0% of the PID output, in 0.1%
0. 0
increments – see Section 5.10.2.
Transition Bandwidth
100. 0
Set the required value between 0.0 and 100.0% of the PID output, in 0.1%
0. 0
increments – see Section 5.10.3.
Output Off Hysteresis Band
25. 0
Set the required value which prevents oscillation of control changes, between 0.0 and
0. 0
25.0% of the PID output, in 0.1% increments.
100
1.5
= 2
0.75
= 33.3%
OFF
' is selected below 0.1.
5.10.3 Calculating the Transition
Bandwidth Value – Fig 5.18
The Transition Bandwidth is the percentage difference of the
proportional band settings.
– if the proportional band settings for the heat output is
Example
20% and for the cool output is 25%:
Transition Bandwidth (%) =
Transition Bandwidth = 20%
If the proportional band settings for both outputs are equal, the
bandwidth is 0%. As a general rule, the Transition Bandwidth
should not exceed 30%.
5 CONTROL OPERATION
25 – 20
x 100
25
33