Programming

4.1.12. communication parameters:

They are defined as follows, according to the mode:
Mode
Default parameters
Programming
9 600 Bauds
no parity
8 data bits
1 stop bit
ASCII
no default parameters defined
®
MODBUS
9 600 Bauds
no parity
8 data bits
1 stop bit
It is possible to choose the delay time of the RTS signal whichever communication mode is
chosen, select this delay from the list of the "RTS signal delay": line. The default parameter is
" norm al", in this case the RTS signal delay depends on the number of characters in the buffer.
Mode
Programming or ASCII
®
MODBUS
Modification of parameters
parameters non modifiable
parameters are defined by using the
SINIT function in the user program
modification of parameters by using
the SINIT function in the user
program
Delay time
System constant KW 00.06
3 characters
KW 00.06 > 1000
1 character
1101 < KW 00.06 < 1355
32 ms
2101 < KW 00.06 < 2355
64 ms
3101 < KW 00.06 < 3355
96 ms
4101 < KW 00.06 < 4355
128 ms
5101 < KW 00.06 < 5355