Reply Times For Modbus Communication - ABB AC 31 Technical Manual

Advant controller 31 40 & 50 series
Hide thumbs Also See for AC 31:
Table of Contents

Advertisement

1.4. Reply times for MODBUS communication

Page 7-10
Communication
The MODBUS processing time depends on:
- The transmission speed
- The number of frame bytes
- The central unit cycle time
- The central unit load factor
The following times are for indication purposes only.
Reply times with a 40 or 50 series central unit
G G G G
Cycle time = 10 ms
Load factor = 80%
Speed = 9 600 Bauds
Nr. of variables
1
10
50
100
150
255
Bits
read (ms)
write (ms)
10 - 60
50
10 - 60
60
10 - 60
110
50 - 60
110
50 - 110
50 - 110
Words
read (ms)
write (ms)
10 - 60
60
10 - 60
110
110 - 170
220
220 -280
390
-
-
-
-
ABB Control - AC 31
1SBC 260400 R1001-b
06.99

Hide quick links:

Advertisement