ABB PST30 Installation And Commissioning Manual page 83

Softstarters
Hide thumbs Also See for PST30:
Table of Contents

Advertisement

Param.
Description
number
58(4)
Locked rotor event of relay V7
58(5)
Underload event of relay V7
58(6)
Phase imbalance event of relay V7
58(7)
PTC event of relay V7
58(8)
Phase reversal event of relay V7
58(9)
Overload warning event of relay V7
58(10)
Thyristor overload warning event of relay
V7
58(11)
High current warning event of relay V7
58(12)
Low current warning event of relay V7
58(13)
Shunt fault event of relay K7
59
Fieldbus control
60
Fieldbus type
61
Fieldbus address
62
Sequence start, number of sequences
63
Start ramp, first sequence
64
Initial voltage, first sequence
65
Current limit, first sequence
66
Setting current, first sequence
67
Start ramp, second sequence
68
Initial voltage, second sequence
69
Current limit, second sequence
70
Setting current, second sequence
71
Start ramp, third sequence
72
Initial voltage, third sequence
73
Current limit, third sequence
74
Setting current, third sequence
75
Language
77
LCD automatic switch-off
78
Password
79
Date type
80
Year
81
Month
82
Day
83
Hour
84
Minutes
97
By-pass doesn't open fault, type of opera-
tion
98
By-pass doesn't close fault, type of opera-
tion
111
Dual current limit time
112
Dual current limit level
113
Fieldbus auto disable
114
Start mode
115
Stop mode
116
Torque limit
117
Tune torque control
123
Analog output
124
Analog output, reference
125
Analog output, type of value
126
Analog output, current range max
1SFC132003M0201
Display text
Setting range
V7 Lock Rot
V7 Underload
V7 Phase Imb
V7 PTC
V7 Phase Rev
V7 Warn OL
V7 Wa SCR OL
V7 Wa I=High
V7 Wa I=Low
K7 Shunt Fault
Fieldb Ctrl
Fieldb Type
AS-Int, Other
Fieldb Addr
0...1000
No of Seq
Start Ramp 1
1...30s, 1...120s
Init Volt 1
30...70%
Curr Lim 1
2.0...7.0xle
1st Set Ie
9.0...1207A
Start Ramp 2
1...30s, 1...120s
Init Volt 2
30...70%
Curr Lim 2
2.0...7.0xle
2st Set Ie
9.0...1207A
Start Ramp 3
1...30s, 1...120s
Init Volt 3
30...70%
Curr Lim 3
2.0...7.0xle
3st Set Ie
9.0...1207A
Language
US/UK, PL, TR, RU,
CN, DE, ES, FR, IT, NL,
PT, SE, FI
LCD Auto Off
1...255min
Password
Date Type
ISO, CE, US
Date Year
1901...2038
Date Month
Date Day
Time Hour
Time Min
BP Closed Op
Stop-M, Stop-A
BP Open Op
Stop-M, Stop-A
C Lim Y Time
0...120 s
C Lim Y Level
2.0...7.0 x Ie
FB Auto Dis
Start Mode
Volt, Torque
Stop Mode
Volt, Torque
Torque Limit
20...200%
Tune T-Ctrl
30...300%
Analog Out
Anl Ref
0...10V, 0...20mA,
4...20mA
Anl Type
I Amp, U Volt, P kW, P
hp, Q kVAr, S kVA, Tmp-
Mot, TmpSCR, cosPhi
I Range Max
10...20000A
Settings and configuration
Default
value
Yes, No
No
Yes, No
No
Yes, No
No
Yes, No
No
Yes, No
No
Yes, No
No
Yes, No
No
Yes, No
No
Yes, No
No
Yes, No
Yes
Yes, No
No
Other
0
No, 2, 3
No
10s
30%
4.0xle
Individual
10s
30%
4.0xle
Individual
10s
30%
4.0xle
Individual
Individual
15min
0...255
0
ISO
Individual
1...12
Individual
1...31
Individual
0...23
Individual
0...59
Individual
Stop-M
Stop-M
0 s
4.0 x Ie
Yes, No
No
Volt
Volt
150%
100%
Yes, No
No
4...20mA
I Amp
PST(B) size
dependent
Chapter 7
Actual
setting
83

Hide quick links:

Advertisement

Table of Contents
loading