1SFC132003M0201

10:15 Start ramp range

Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Start Range
The time of the start ramp is settable up to 30 seconds as
default, but if required the range could be extended up to 120
seconds by this parameter.
A too long ramp time will increase the risk of tripping the
overload protection.
Parameter
Default value Setting range
text
Start Range 1-30 s

10:16 Stop ramp range

Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Stop Range
The time for the stop ramp is settable up to 30 seconds as
default, but if required the range could be extended up to 120
seconds by this parameter.
Parameter
Default value Setting range
text
Stop Range 0-30 s
Description
1-30 s, 1-120 s
Selectable
range for start
ramp
Description
0-30 s, 0-120 s
Selectable range
for stop ramp
Chapter 10
Functions
139