10:34 High current protection, type of
operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/High I/High I Op
This parameter makes it possible to select between three
different actions of the softstarter when the protection is
activated. It is active only if the high current protection is
selected.
Stop–M
The motor stops and a manual reset is required
before restart.
Stop–A
The motor stops and an automatic reset is
performed when the fault disappears.
Ind
The motor continues to run but a fault indication
is given.
Parameter
Default value
text
High I Op
Stop–M

10:35 Phase reversal protection

Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/Phase Rev
The softstarter accepts any phase sequence but if this
protection is selected, the phase sequence must be L1, L2,
L3, or else the protection is activated.
Parameter
Default value Setting range
text
Phase Rev No
Setting range
Description
Stop–M, Stop–A,
Type of opera-
Ind
tion for high cur-
rent protection
Description
Yes, No
Phase reversal
protection
Chapter 10
Functions
149