1SFC132003M0201
Chapter 10 Functions
This chapter describes all settings and functions possible in
the softstarter, as well as the easiest way of finding them. The
respective default values, setting ranges and parameter texts
shown in the display are also stated.
10:1 Setting current
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Setting Ie
The setting of this parameter shall be according to the current
the softstarter is exposed to. If the motor is connected In
Line, set the rated motor current (see rating plate on the
motor).
If the motor is connected Inside Delta, set the current in the
Delta circuit calculated by rated motor current divided by
=58 % of the rated motor current.
⁄
(
)
1
3
Parameter
Default value Setting range
text
Setting Ie
Individual
(size related)
Description
9...1207A divided
Rated motor cur-
into 19 overlap-
rent
ping ranges
Chapter 10
Functions
131