Chapter 6
Human-Machine Interface (HMI)
Top level
Settings
Local Control
Event Log
Status Information
Reset Events
Figure 21: Local control menu
Top level
Settings
Local Control
Event Log
Status Information
Reset Events
Figure 22: Start/Stop menu
70

6:2.4 Local Control menu

The Local Control menu is used to start or stop the motor
from the keypad. When a type of local control is selected the
softstarter can only be controlled by the keypad.
The softstarter operation state (stopped/running) remains
when selecting local control until it is changed there.
Previous type of control is activated again when the local
Start/Stop
control is exited.
Three different selections are possible (see the table below).
Jog
Press navigation keys to view different types of control.
DOL Start
The LOCAL CONTROL menu can not be entered if Sequence
start is selected.
Once the motor has been started in this menu, it must first be
stopped before you leave the menu. If the motor is already
running when the menu is entered it is possible to leave
immediately without stopping the motor.
Function
Start/stop
Jog
DOL start
(PSTB370...PSTB1050
only)

6:2.4.1 Start/Stop the motor

Start
Enter the Start/Stop menu, figure 22.
Select Start. The motor will now start and run according to
Start/Stop
the set parameters.
Stop
Jog
Select Stop. The motor will stop according to the set
DOL Start
parameters. It is possible to press stop command during the
start ramp if required.
Description
To start and stop the motor with
the keypad.
To run the motor as long as Jog is
pressed.
To start and stop the motor with
the built-in by-pass contactor.