Chapter 7
Settings and configuration
Settings
Functional Settings
Figure 32: Outputs groups
106

7:2.4.7 Outputs

To set parameters related to the programmable outputs,
Start/Stop
enter the Outputs group.
Torque control
Output relay K4 (Relay K4)
Protections
Select the required function for the output relay K4.
One of the following functions can be selected:
Warnings
Run
Faults
TOR
Inputs
Event
Outputs
Analog Output
Fieldbus
Seq Start
Press Store to save/activate the selected function.
Output relay K5 (Relay K5)
Select the required function for the output relay K5.
One of the following functions can be selected:
Run
TOR
Event
Press Store to save/activate the selected function.
Run indication.
Top of ramp indication.
Indication of selected event(s) where following
functions can be selected individually:
• Overload protection
• Fault
• High current protection
• Thyristor overload protection
• Locked rotor protection
• Underload protection
• Phase imbalance protection
• PTC protection
• Phase reversal protection
• Overload warning
• Thyristor overload warning
• High current warning
• Low current warning
• Shunt Fault
Run indication.
Top of ramp indication.
Indication of selected event(s), see relay K4.
1SFC132003M0201