1SFC132003M0201
10:19 Overload protection, dual type,
start class
Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/Overload/Dual Class S
This parameter makes it possible to set the required class of
the overload protection during start. When full voltage is
reached there will be a switch-over to run class after 30
seconds. (see below).
Parameter
Default value Setting range
text
OL Class S 10
10:20 Overload protection, dual type, run
class
Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/Overload/Dual Class R
This parameter makes it possible to set the required class of
the overload protection for continuous run. The run class is
activated 30 seconds after full voltage has been reached.
Parameter
Default value Setting range
text
OL Class R 10
Description
10A, 10, 20, 30
Overload class,
Dual type, Start
Class
Description
10A, 10, 20, 30
Overload class,
Dual type, Run
Class
Chapter 10
Functions
141