Supply Voltage And Control Circuit; Supply Voltage, Terminals 1 And 2; Earthing, Terminal 3 - ABB PST30 Installation And Commissioning Manual

Softstarters
Hide thumbs Also See for PST30:
Table of Contents

Advertisement

Figure 7: Supply voltage
Figure 8: Function earth
1. . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 9: Tightening torques and cable dimensions (1 mm=0.0394 in)
1SFC132003M0201

5:2.2 Supply voltage and control circuit

When used for marine applications, and if feeding from the
outside of the enclosure, then please use a standard cable
for feeding the supply voltage and for the control circuit, with
an auxiliary bare conductor (earth conductor) and make a
360 degree connection to earth in the glands, or close to the
glands. As long as these cables / wires are only internal
wiring, inside the enclosure, there is no need for the 360
degree earth connections / protections.

5:2.2.1 Supply voltage, terminals 1 and 2

Connect neutral and phase to terminal 1 and 2.
Check that you have the correct supply voltage U

5:2.2.2 Earthing, terminal 3

Connect the cable to a earthing point close to the softstarter.
The cable should be as short as possible. A suitable earthing
point would be next to the softstarter on the mounting plate,
see Figure 8. The mounting plate should also be earthed.
This is not a protective earth, it is a function earth. The
earthing cable should be as short as possible. Maximum
length 0.5 m.
M3
0,5 Nm - 4,3 lb.in
3,5x0,6
Chapter 5
Connection
.
s
0,14 ... 2,5 mm
2
AWG 12 ... 22
0,14 ... 2,5 mm
2
47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents