1SFC132003M0201
10:43 Low current warning level
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn I=Low/Wa I=L Lev
This parameter makes it possible to set the indication level of
the low current warning function.
Parameter
Default value Setting range
text
Wa I = L Lev 0.8 x I
10:44 Overload warning
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn OL
If the function is selected a warning signal will be given that
the overload protection will be activated, if the motor load
does not decrease.
Parameter
Default value Setting range
text
Warn OL
No
10:45 Overload warning level
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn OL/Wa OL Lev
This parameter makes it possible to set the indication level of
the motor overload protection. The actual trip level of the
protection is represented by 100%.
Parameter
Default value
text
Wa OL Lev 90%
0.4...1.0 x I
e
e
Yes, No
Setting range
40...99%
Chapter 10
Functions
Description
Trip level for
low current
warning
Description
Overload warning
Description
Trip level for
overload warning
153