Appendix A
Power Supply Specifications
Table A-19 6000 W AC-Input Power Supply Specifications (continued)
Specification
System power dissipation
Branch circuit requirement (AC-input)
Power supply output
Output holdup time
Heat Dissipation
OL-5781-04
Description
7034 W
Each power supply input should have its own
dedicated, fused-branch circuit:
•
For North America—20 A
•
For International—Circuits should be sized
according to local and national codes
•
All Catalyst 6500 series AC-input power supplies
require single-phase source AC.
•
All AC power supply inputs are fully isolated.
Source AC can be out of phase between
–
multiple power supplies in the same chassis,
which means that PS1 can be operating from
phase A and PS2 can be operating from
phase B.
Source AC can be out of phase between AC
–
inputs on power supplies that are equipped
with multiple AC inputs, which means that
power cord 1 can be plugged into phase A and
power cord 2 can be plugged into phase B.
2900 W operation (one 220 VAC source or two
•
110 VAC sources)
25 A @ +3.3 V
–
12 A @ +12 V
–
63.6 A @ +42 V
–
6000 W operation (two 220 VAC sources)
•
25 A @ +3.3 V
–
–
12 A @ +12 V
–
137.4 A @ +42 V
20 ms minimum
•
23,812 BTU/hour (approx.)
Catalyst 6500 Series Switches Installation Guide
6000 W AC-Input Power Supply
A-45