Cisco 6509 - Catalyst Chassis Switch Installation Manual page 255

Installation guide
Table of Contents

Advertisement

Appendix A
Power Supply Specifications
Table A-19 6000 W AC-Input Power Supply Specifications (continued)
Specification
System power dissipation
Branch circuit requirement (AC-input)
Power supply output
Output holdup time
Heat Dissipation
OL-5781-04
Description
7034 W
Each power supply input should have its own
dedicated, fused-branch circuit:
For North America—20 A
For International—Circuits should be sized
according to local and national codes
All Catalyst 6500 series AC-input power supplies
require single-phase source AC.
All AC power supply inputs are fully isolated.
Source AC can be out of phase between
multiple power supplies in the same chassis,
which means that PS1 can be operating from
phase A and PS2 can be operating from
phase B.
Source AC can be out of phase between AC
inputs on power supplies that are equipped
with multiple AC inputs, which means that
power cord 1 can be plugged into phase A and
power cord 2 can be plugged into phase B.
2900 W operation (one 220 VAC source or two
110 VAC sources)
25 A @ +3.3 V
12 A @ +12 V
63.6 A @ +42 V
6000 W operation (two 220 VAC sources)
25 A @ +3.3 V
12 A @ +12 V
137.4 A @ +42 V
20 ms minimum
23,812 BTU/hour (approx.)
Catalyst 6500 Series Switches Installation Guide
6000 W AC-Input Power Supply