Honeywell SmartLine ST 700 User Manual page 75

Pressure transmitters
Hide thumbs Also See for SmartLine ST 700:
Table of Contents

Advertisement

Calibrate Low Correct
[31LO COR]
Calibrate High Correct
[32 HI COR]
Screen Rotation
[33 SCRROT]
Revision 13
Two-point Field
Accuracy Calibration
Method for DP/AP/GP
transmitters
Two-Point Field
Accuracy Calibration
Method for DP/AP/GP
transmitters
OFF
ON
ST 700 SmartLine Pressure Transmitters User's Manual
Not normally used. See Field
Calibration for Alternate Ranges,
below.
Executing this selection corrects
input pressure to be at or near
the Cal Low Point without
compromising LRV and URV
corrections. A trial-and-error
approach using different Cal
Adjust Ratio values and repeated
executions of Cal Low Correct
followed by Cal High Correct may
be required.
The live value of the primary
pressure input is shown on this
display so the user can easily see
the result of the correction.
Note: Cal Low Correct must be
performed before Cal High
Correct, but Cal High Correct
may be repeated as necessary.
Not normally used. See Field
Calibration for Alternate Ranges,
below.
Executing this selection corrects
input pressure to be at or near
the Cal High Point without
compromising LRV and URV
corrections. A trial-and-error
approach using different Cal
Adjust Ratio values and repeated
executions of Cal Low Correct
followed by Cal High Correct may
be required.
The live value of the primary
pressure input is shown on this
display so the user can easily see
the result of the correction.
Note: Cal Low Correct must be
performed before Cal High
Correct, but Cal High Correct
may be repeated as necessary.
Automatic display screens switch
function.:
Select 'ON' or 'OFF' to rotate
display screens automatically.
Press  to
enter menu
selection
Press  to
initiate action
Press  to
enter menu
selection
Press  to
initiate action
Press  to
enter menu
selection
Menu to
select from
list
 to enter
Page 59