Honeywell SmartLine ST 700 User Manual page 201

Pressure transmitters
Hide thumbs Also See for SmartLine ST 700:
Table of Contents

Advertisement

Calibrate Low
Two-point Field Accuracy
Correct
Calibration Method for
[31LO COR]
DP/AP/GP transmitters
Calibrate High
Two-Point Field Accuracy
Correct
Calibration Method for
[32 HI COR]
DP/AP/GP transmitters
Revision 12
ST 700 SmartLine Pressure Transmitters User's Manual
Not normally used. See
Field Calibration for
Alternate Ranges, below.
Executing this selection
corrects input pressure to be
at or near the Cal Low Point
without compromising LRV
and URV corrections. A
trial-and-error approach
using different Cal Adjust
Ratio values and repeated
executions of Cal Low
Correct followed by Cal High
Correct may be required.
The live value of the primary
pressure input is shown on
this display so the user can
easily see the result of the
correction.
Note: Cal Low Correct must
be performed before Cal
High Correct, but Cal High
Correct may be repeated as
necessary.
Not normally used. See
Field Calibration for
Alternate Ranges, below.
Executing this selection
corrects input pressure to be
at or near the Cal High Point
without compromising LRV
and URV corrections. A
trial-and-error approach
using different Cal Adjust
Ratio values and repeated
executions of Cal Low
Correct followed by Cal High
Correct may be required.
The live value of the primary
pressure input is shown on
this display so the user can
easily see the result of the
correction.
Note: Cal Low Correct must
be performed before Cal
High Correct, but Cal High
Correct may be repeated as
necessary.
Press  to
enter menu
selection
Press  to
initiate action
Press  to
enter menu
selection
Press  to
initiate action
Page 185

Advertisement

Table of Contents
loading

Table of Contents