20. Loosen the set screw ½- turn.
21. Rotate the housing to the desired position (Max. 180
screw.
22. Carefully align and connect the Sensor Ribbon Cable to connector "J4" at the bottom of the
communication module board. When installing the communication module in the next step,
be careful not to pinch the Sensor Ribbon Cable.
23. Carefully, insert the communication module into the Electronics compartment. Ensure that
the Sensor Ribbon Cable is not pinched.
24. Tighten the two communication module retaining screws.
25. If applicable, re-install the display module as follows:
a. Orient the display as desired.
b. Install the Interface connector in the display module such that it will mate with
the socket for the display in the communication module.
c. Carefully line up the display, and snap it into place. Verify that the two tabs on
the sides of the display latch.
Orient the display for proper viewing through the end cap window.
You can rotate the meter mounting orientation in 90 o increments.
26. Connect the bracket to the transmitter housing.
27. Recalibrate the transmitter per section
28. Return the transmitter to service, and turn ON power.
29. Verify the transmitter configuration data. Update the configuration if necessary.
30. Lubricate the end-cap O-ring with Parker Super O-ring silicone lubricant or equivalent before
replacing the end caps.
Page 98
7 Calibration,