Honeywell SmartLine ST 700 User Manual page 258

Pressure transmitters
Hide thumbs Also See for SmartLine ST 700:
Table of Contents

Advertisement

A3. Hazardous Area Certifications
MSG
CODE
AGENCY
Explosionproof:
Class I, Division 1, Groups A, B, C, D;
Dust Ignition Proof:
Class II, III, Division 1, Groups E, F, G;
T6..T5
Class l, Zone 0/1, AEx db IIC T6..T5
Ga/Gb
Class ll, Zone 21, AEx tb IIIC T95
Intrinsically Safe:
Class I, II, III, Division 1, Groups A, B, C,
D, E, F, G: T4
FM
Class l, Zone 0, AEx ia IIC T4 Ga
T
Approvals
A
FISCO Field Device (Only for FF Option)
M
Ex ia IIC T4 Ga; Ex ic IIC T4 Gc
USA
Nonincendive:
Class I, Division 2, Groups A, B, C, D
locations, T4
Class l, Zone 2, AEx nA IIC T4 Gc
Enclosure: Type 4X/ IP66/ IP67
STANDARDS: FM Class 3600:2011; FM Class 3610: 2010; FM Class 3611: 2004; FM
Class 3615: 2006; FM Class 3616: 2011; FM Class 3810: 2005; ANSI/ISA 60079-0: 2013;
ANSI/UL 60079-1: 2015; ANSI/UL 60079-11: 2014; ANSI/ISA 60079-15: 2012; ANSI/UL
60079-26: 2017; ANSI/UL 60079-31: 2015; ANSI/NEMA 250: 2003; ANSI/ IEC 60529:
2004
Explosion Proof:
Class I, Division 1, Groups A, B, C, D;
Class II, Division 1, Groups E, F, G;
Class III, Division 1, T6..T5
Class I Zone 1 AEx db IIC T6..T5 Ga/Gb
Ex db IIC T6..T5 Ga/Gb
Zone 22 AEx tb IIIC T95
Ex tb IIIC T95
Intrinsically Safe:
Canadian
Class I, II, III, Division 1, Groups A, B, C,
Standards
D;
Association
Class II, Division 1, Groups E, F, G;
B
(CSA)
Class III, Division 1, T4
USA and
Class I Zone 0, AEx ia IIC T4 Ga
Canada
Class I Zone 2, AEx ic IIC T4 Gc
Ex ia IIC T4 Ga
Ex ic IIC T4 Gc
FISCO Field Device (Only for FF Option)
Ex ia IIC T4 Ga;
Ex ic IIC T4 Gc
Nonincendive:
Class I, Division 2, Groups A, B, C, D;
Class II, Division 2, Groups F, G;
Class III, Division 2, T4
Page 242
TYPE OF PROTECTION
o
Db
o
Db
ST 700 SmartLine Pressure Transmitters User's Manual
ELECTRICA
COMM.
OPTION
PARAMETER
All
o
Db
4-20 mA /
DE/ HART
Foundation
Fieldbus
4-20 mA /
DE/ HART/
Foundation
Fieldbus
All
All
4-20 mA /
DE/ HART
Foundation
Fieldbus
4-20 mA /
DE/ HART/
Foundation
Fieldbus
L
AMBIENT
TEMP (Ta)
S
T5: -50 ºC to
85ºC
Note 1
T6: -50 ºC to
65ºC
Note 2a
-50 ºC to 70ºC
-50 ºC to 70ºC
Note 2b
Note 1
-50 ºC to 85ºC
All
-
o
T5: -50
C TO
o
85
C
Note 1
o
T6: -50
C TO
o
65
C
o
o
Note 2
-50
C TO 70
o
o
-50
C TO 70
Note 2
o
o
Note 1
-50
C to 85
C
Revision 13
C
C