Honeywell SmartLine ST 700 User Manual page 195

Pressure transmitters
Hide thumbs Also See for SmartLine ST 700:
Table of Contents

Advertisement

aтм (atm)
Бар (bar)
ftH2O68F
гс/см2 (gf/cm2)
inH2O39F
inH2O60F
inH2O68F
inHg0C
кгс/см2 (kgf/cm2)
кПа (kPa)
мБар (mbar)
ммH2O4C (mmH2O4C)
1Ед.Изм
ммH2O68F (mmH2O68F)
[1UNITS]
mmHg0C (ммHg0C)
МПа (MPa)
Па (Pa)
пси (psi)
торр (Torr)
мH2O4С (mH2O4C)
смH2O4C (cmH2O4C)
2ВвдLRV
[ 2ENTLRV]
###. ##
###. ##
3ВвдURV
[ 3ENTURV]
4УстНол
Zero Trim
[4SETZRO]
5НолЦАП
[5ZEROTR]
DAC Zero Trim
Note: Loop must be
removed from
Automatic Control
Revision 12
ST 700 SmartLine Pressure Transmitters User's Manual
Choose appropriate
engineering units from list
This selection determines
the units of the values
shown on the following
menu items:
Enter LRV
Enter URV
Set LRV
Set URV
Zero Correct
LRV Correct
URV Correct
Cal Low Point
Cal High Point
Cal Low Correct
Cal High Correct
Barometric Correct
For calibration, this
parameter allows the user to
match the value displayed
on the menus to the units
supported by the user's
calibration equipment.
The limits are:
2X the Lower Range Limit
(LRL) of the Meter body and
2X the Upper Range Limit
(URL) of the Meter body.
The LRV/URV value will be
available in Pressure Units
(Simple Display pressure
unit)
perform an input calibration
correction by applying
process input at zero.
This selection allows the
loop zero output 4mA value
to be trimmed.
Note: You must connect a
current meter to the
transmitter to monitor the
loop output.
Press  to
enter menu
selection
Menu to
select from
list
 to enter
Press  to
enter menu
selection
 Menu to
select
number.
 to enter
and shift to
the next digit
to the right
Press  to
enter menu
selection
Press  to
initiate action
Press  to
enter menu
selection
 Menu to
select
number.
 to enter
and shift to
Page 179