Constant Current Source Mode Procedure; Figure 56 - St 700 Basic Transmitter - Current Loop Test Connections - Honeywell SmartLine ST 700 User Manual

Pressure transmitters
Hide thumbs Also See for SmartLine ST 700:
Table of Contents

Advertisement

12.8.4 Constant Current Source Mode Procedure

Figure 56 – ST 700 Basic Transmitter - Current Loop Test Connections
1. Refer to Figure 56 for test connections. Verify the integrity of electrical components in the
output current loop.
2. Establish communication with the transmitter. For these procedures, the values of
components in the current loop are not critical if they support reliable communication
between the transmitter and the Toolkit.
3. On the Toolkit, display the Output Calibration box.
4. In the Output Calibration box, select the Loop Test button; the LOOP TEST box will be
displayed.
5. Select the desired constant-level Output: 0%, 100%, or Other (any between 0% - 100%).
6. Select the Set button. A box will be displayed asking Are you sure you want to place the
transmitter in output mode?
With the transmitter in Analog mode, you can observe the output on an externally-
connected meter or on a local meter. In DE mode, you can observe the output on the local
meter or on the Toolkit Monitor display.
7. Select the Yes button. Observe the output current at the percentage you selected in Step 5.
8. To view the monitor display, navigate back from the LOOP TEST display, and select the
MONITOR display. A Confirm popup will be displayed.
9. Select Yes to continue. This concludes the Startup procedure.
Revision 12
ST 700 SmartLine Pressure Transmitters User's Manual
Page 157

Advertisement

Table of Contents
loading

Table of Contents