Parameter settings

The following table lists the parameters that can be set for the NZ2FTS-60DA4.
Item
AO 0 (Channel 0) to
AO 3 (Channel 3)
*1 (0) to (8) are the values set in the register when the digital I/O module is connected to the NZ2FT-MT or the NZ2FT-EIP.

Process data

The following table lists the Process data of the NZ2FTS-60DA4.
Input/
Address
Output
(byte)
Output
0 to 1
2 to 3
4 to 5
6 to 7
17 ANALOG OUTPUT MODULE
496
17.1 NZ2FTS-60DA4
Description
Data format
Sets the resolution of AO values.
For the maximum resolution and AO value of each analog output
range, refer to the following.
Page 489 Performance specifications
Output range
Switches the analog output range for each channel. Switching the
range changes output conversion characteristic too.
Substitute value
Performs analog output using the preset value when a fieldbus error
occurs.
It depends on the setting of the parameter "Output behaviour on
fieldbus error" of the coupler.
Description
AO 0 (Channel 0)
AO 1 (Channel 1)
AO 2 (Channel 2)
AO 3 (Channel 3)
*1
Setting range
• Normal resolution format (0)
• High resolution format (1)
(Default: High resolution format)
• 0 ... 20mA (0)
• 4 ... 20mA (1)
• 0 ... 10V (2)
• -10 ... 10V (3)
• 0 ... 5V (4)
• -5 ... 5V (5)
• 1 ... 5V (6)
• 2 ... 10V (7)
• Disabled (8)
(Default: Disabled)
• -32768 to 32767 (16-bit signed
binary value)
(Default: 0)
Data format
Word
Word
Word
Word