Confirmation By Status Information (Standard/Extended Diagnosis) - Mitsubishi Electric NZ2FTGN User Manual

Slice remote i/o module
Table of Contents

Advertisement

Confirmation by status information (Standard/Extended
Diagnosis)
Standard Diagnosis shows the status of the NZ2FT-PBV, and Extended Diagnosis shows the I/O module status and alarm
occurrence.
Standard/Extended Diagnosis is automatically stored asynchronously in the buffer memory of the master module.
Assignment of the master module to the buffer memory
The following describes the situation where the master module is the RJ71PB91V.
Buffer memory of the master module
Address
Address
(decimal)
(hexadecimal)
23072 to 23321
5A20H to 5B19H
23328 to 23454
5B20H to 5B9EH
23456
5BA0H
23457 to 23583
5BA1H to 5C1FH
NZ2FT-PBV Standard/Extended Diagnosis
Name
Size
Name
Diagnostic
250 words
Refers to the following data from
information area
Standard Diagnosis.
• Status 1
• Status 2
• Status 3
• NZ2FT-PBV FDL address
Extended
127 words
Standard Diagnosis
diagnostic
Extended
information area
Diagnosis
Extended
1 word
Set the FDL address of the NZ2FT-PBV
diagnostic
for the destination where the extended
information read
diagnostic information is read.
request area
Extended
127 words
The same data structure as the extended
diagnostic
diagnostic information area
information read
response area
Reference
Page 258 Standard Diagnosis
Page 258 Standard Diagnosis
Identifier Related Diagnosis
Page 259 Identifier Related Diagnosis
Module Status
Page 260 Module Status
Channel Related Diagnosis
Page 261 Channel Related Diagnosis
Diagnostic alarm
Page 261 Diagnostic alarm
10 NZ2FT-PBV
255
10.9 Troubleshooting