Performance Specifications - Mitsubishi Electric NZ2FTGN User Manual

Slice remote i/o module
Table of Contents

Advertisement

Performance specifications

This section describes the performance specifications of the NZ2FTS3-4R. ( Page 30 General Specifications)
Item
System bus transfer speed
Number of points
Output type
Response time
Maximum output current
Switching frequency
Supply to external device
Short circuit protection
Protection circuit
Life (15VAC, load current 1A)
Module diagnostics
External power supply voltage
Input power supply current consumption
Current consumption of external power supply for output part
Weight
Derating
The following figure shows the derating curve of the maximum switching voltage for the resistive load of the NZ2FTS3-4R.
[V]
300
200
100
50
40
30
20
10
0.1
0.2
0.5
15 DIGITAL OUTPUT MODULE
472
15.7 NZ2FTS3-4R
Per channel
Per module
Resistive load (47 minimum)
1
2
5
10
NZ2FTS3-4R
48Mbps
4
Relay output
20ms
Between 55 and 60: 5A
55 or lower: 6A
(IECEx/ATEX: Between 55 and 60: 2.4A)
(IECEx/ATEX: 55 or lower: 3A)
Between 55 and 60: 20A
55 or lower: 24A
(IECEx/ATEX: Between 55 and 60: 9.6A)
(IECEx/ATEX: 55 or lower: 12A)
5Hz maximum
Not available
Not available
6A external fuse
300.000 times or more
Available
24VDC +20%/-15%
35mA
4mA + 4mA/active relay
117g
20
[A]

Advertisement

Table of Contents
loading

Table of Contents