Wiring products for NZ2FT-BT

Use a product that meets the following standards for wiring.
Network type
Name
CC-Link
Ver.1.10-compatible
CC-Link dedicated
cable
Terminating resistor

Wiring products for NZ2FT-PBV

Use a product that meets the following standards for wiring.
Network type
Name
PROFIBUS-DP
PROFIBUS cable

Wiring products for NZ2FTS2-4A

Install a 4A slow fuse.

Wiring products for NZ2FT-C24

Connection with RS-232
Use a shielded cable that meets the following standards.
Available device
Name
NZ2FT-C24
Cable
The following table shows the maximum cable length when connecting via RS-232.
Cable capacitance
2500pF
55pF/m
Connection with RS-485 or RS-422
Use a shielded cable that meets the following standards.
Available device
Name
NZ2FT-C24
Cable
• The following table shows the maximum cable length when connecting via RS-485 or RS-422.
Transmission speed
19200kbps
28800kbps
38400kbps
57600kbps
115200kbps
• Terminate both ends of the cable.
• For RS-485, use a single-core pair for the communication line. There are no restrictions on COM. Ground the other wires.
• For RS-422, connect the transmission (TXD+/TXD-) communication lines and the reception (RXD+/RXD-) communication
lines in pairs. There are no restrictions on COM. Ground the other wires.
3 INSTALLATION AND WIRING
42
3.3 Wiring Products
Connector
Socket for 5-pole PCB plug-in connector (screw
connection)
Connector
D-Sub9 pin connector
Screw size: #4-40 UNC
Connector
• NZ2FT-C24 side: Spring clamp terminal block
• External device side: Connector compatible
with external devices
Maximum cable length
15m, shielded
45m
Connector
• NZ2FT-C24 side: Spring clamp terminal block
• External device side: Connector compatible
with external devices
Maximum cable length
1200m, shielded
850m
500m
250m
200m
Standard
Shielded twisted pair cable
CC-Link Partner Association website: http://www.cc-
link.org/
If the NZ2FT-BT is the terminal station, a terminating
resistor (110) is necessary.
Standard
Shielded twisted pair cable
Compliant with the open network PROFIBUS
standardized by the international standard IEC 61158
Standard
LIYCY 0.14 or 0.34
Recommended: Weidmüller PAC-UNIVD9M-F-1M5, Order
No. 1350400015
Standard
Twisted pair cable (U/UTP, Type Cat-3 or J-2YY-2x2x0,6)
Recommended: LiYCY or LiYY 0.25