2.2

General Specifications

Item
Operating ambient temperature
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Shock resistance
Operating atmosphere
*1
Operating altitude
Storage altitude
Installation location
*3
Overvoltage category
*4
Pollution degree
Equipment class
*1 Do not use or store the coupler and I/O modules under pressure higher than the atmospheric pressure of altitude 0m. Doing so may
cause malfunction. To use the modules under high pressure, please consult your local Mitsubishi representative.
*2 If the environment satisfies the operating ambient temperature, operating ambient humidity, and other conditions, the module can be
used even outside the control panel.
*3 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within the premises.
Category  applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for
equipment with a rated voltage of 300V or less is 2500V.
*4 This index indicates the degree to which conductive material is generated in the environment in which the equipment is used.
In pollution degree 2, only non-conductive pollution occurs. A temporary conductivity caused by condensing may be expected
occasionally.
To compliant with EMC Directive, refer to the following.
Page 585 EMC and Low Voltage Directives
2 OVERVIEW OF NZ2FT SYSTEM
30
2.2 General Specifications
Specifications
Coupler
I/O module
-40 to 85
Coupler
I/O module
Coupler
I/O module
Compliant with JIS C 60068-2-6 and IEC 60068-2-6
• 5 to 8.4Hz: Half amplitude 3.5mm
• 8.4 to 150Hz: Acceleration 1g
Compliant with JIS C 60068-2-27 and IEC 60068-2-27 (15g over 11ms, sine half-wave pulse)
No corrosive gas or flammable gas
0 to 2000m
0 to 3000m
*2
Inside a control panel
 or lower
2 or less
Class I
For horizontal installation
For vertical installation
-20 to 60
10 to 95%RH, non-condensing
5 to 95%RH, non-condensing
10 to 95%RH, non-condensing
5 to 95%RH, non-condensing
• -20 to 60 (when 2  8A is
supplied)
• -20 to 55 (when 2  10A is
supplied)
• -20 to 55 (when 2  6A is
supplied)
• -20 to 50 (when 2  8A is
supplied)