Example using the NZ2FTS-60RD4

This program reads Process alarm data when Process alarm occurs in RTD 0 (Channel 0) to RTD 3 (Channel 3) of the
temperature input module (Resistance Temperature Detector).
System configuration
RJ71PB91V
Item
DP-Master (FDL address 0)
DP-Slave (FDL address 1)
Device assignment
The following figure shows the device assignment for communications that use the alarm acquisition function. ( Page 234
Checking warning output (Process alarm))
Master station
CPU module
Device/label memory
D2007
·
D2008
CPU module
Power supply module
PROFIBUS-DP module
PROFIBUS-DP compatible coupler
4ch analog temperature input module (RTD)
Slave station
RJ71PB91V
Buffer memory
(input data area)
U0\G26453
·
U0\G26454
NZ2FT-PBV
Model
R04CPU
R61P
RJ71PB91V
NZ2FT-PBV
NZ2FTS-60RD4
NZ2FT-PBV
Input data
Byte
Content
0
Process alarm
·
data (4bytes)
3
10.8 Program Example of NZ2FT-PBV
NZ2FTS-60RD4
Process alarm data
Byte
Content
0
High alarm (1byte)
1
Low alarm (1byte)
2
16 Bit Time stamp
(2bytes)
3
10 NZ2FT-PBV
10
249