Option handling
Set each I/O module to stop/operate while the NZ2FT system is operating.
If I/O control is not to be performed for a specific I/O module for a certain period of time, set that I/O module to stop. By doing
so, an error resulting from disconnecting the electronic unit part can be suppressed. ( Page 55 Removing electronic unit
part)
The following operations are required to set the I/O module to stop/operate.
• Set the parameter "Option handling" to "Enabled". ( Page 209 GX Configurator-PN)
• Write Dataset to the NZ2FT-PN. ( Page 178 Dataset)
Dataset is created and written with a program. ( Page 182 Option handling program example)
Operation until stop
The following describes the operations to be performed to set an I/O module to stop, including those to be performed after the
electronic unit part is disconnected and after Dataset is written and the stop operation is set.
Ex.
The "Overview" window of the Web server transitions as follows.
Item
During operation
Removing electronic unit part
Before setting Option handling
Write Dataset
In stopped state
9 NZ2FT-PN
174
9.4 Functions
"Overview" window
Window description
The modules with the following slot numbers are displayed.
• Slot number 00: NZ2FT-PN
• Slot number 01: NZ2FTS4-4DE
• Slot number 02: NZ2FTS3-8DE (stop target)
• Slot number 03: NZ2FTS1-16DE
• Slot number 04: NZ2FTS-60AD4
The I/O module to be stopped (slot number 02) is displayed
semi-transparently.
The I/O module in stopped state is hidden and the slot number
display is justified to the left.