Honeywell SmartVFD HVAC MR4 User Manual page 97

Variable frequency drives for constant and variable torque applications
Table of Contents

Advertisement

Honeywell
• 25
3.4
Monitor group
The drive provides you with a possibility to monitor the actual values of parameters and signals
as well as statuses and measurements. Some of the values to be monitored are customizable.
3.4.1
Multimonitor
On the multi-monitor page, you can collect nine values that you wish to monitor. See page 13
for more information.
3.4.2
Basic
See Table 14 in which the basic monitoring values are presented.
NOTE!
Only Basic I/O board statuses are available in the Monitor menu. Statuses for all I/O board
signals can be found as raw data in the I/O and Hardware system menu.
Check expander I/O board statuses when required in the I/O and Hardware system menu.
Monitoring value
M2.2.1
Output frequency
M2.2.2 Frequency reference
M2.2.3
Motor speed
M2.2.4
Motor current
M2.2.5
Motor torque
M2.2.7
Motor shaft power
M2.2.8
Motor shaft power
M2.2.9
Motor voltage
M2.2.10
DC link voltage
M2.2.11
Unit temperature
M2.2.12
Motor temperature
M2.2.13
Analog input 1
M2.2.14
Analog input 2
M2.2.15
Analog output 1
M2.2.16
Motor preheat
M2.2.17
Drive Status Word
M2.2.18
Last active fault
Unit
ID
Hz
1
Output frequency to motor
Hz
25
Frequency reference to motor control
rpm
2
Motor speed in rpm
A
3
%
4
Calculated shaft torque
%
5
Total power consumption of AC drive
kW/hp
73
V
6
V
7
°C
8
Heatsink temperature
%
9
Calculated motor temperature
%
59
Signal in percent of used range
%
60
Signal in percent of used range
%
81
Signal in percent of used range
1228
0 = OFF
1 = Heating (feeding DC-current)
43
Bit coded status of drive
B1=Ready
B2=Run
B3=Fault
B6=RunEnable
B7=AlarmActive
B10=DC Current in stop
B11=DC Brake Active
B12=RunRequest
B13=MotorRegulatorActive
37
The fault code of latest activated fault
that has not been reset.
HVAC A