Group 3.5: I/O Configuration
3.5.7.1
Digital inputs
Digital inputs are very flexible to use. Parameters are functions that are connected to the re-
quired digital input terminal. The digital inputs are represented as, for example, DigIN Slot A.2,
meaning the second input on slot A.
It's also possible to connect the digital inputs to time channels which are also represented as
terminals.
Code
Parameter
M3.5.1.1
Control signal 1 A
M3.5.1.2
Control signal 2 A
M3.5.1.3
Control signal 1 B
M3.5.1.4
Control signal 2 B
M3.5.1.5
I/O B control force
M3.5.1.6
I/O B reference force
M3.5.1.7
External fault close
M3.5.1.8
External fault open
M3.5.1.9
Fault reset
M3.5.1.10
Run enable
M3.5.1.11
Run interlock 1
M3.5.1.12
Run interlock 2
Acceleration/Decelera-
M3.5.1.13
tion time selection
M3.5.1.14
Motor preheat ON
M3.5.1.15
Fire Mode activation
Preset frequency selec-
M3.5.1.16
tion 0
Preset frequency selec-
M3.5.1.17
tion 1
Preset frequency selec-
M3.5.1.18
tion 2
M3.5.1.19
Timer 1
M3.5.1.20
Timer 2
M3.5.1.21
Timer 3
M3.5.1.22
PID1 setpoint boost
Default
ID
Start signal 1 when control place is I/O 1
DigIN SlotA.1
403
(FWD)
Start signal 2 when control place is I/O 1
DigIN Slot0.1
404
(REV)
DigIN Slot0.1
423
Start signal 1 when control place is I/O B
DigIN Slot0.1
424
Start signal 2 when control place is I/O B
DigIN Slot0.1
425
TRUE = Force the control place to I/O B
TRUE = Used frequency reference is speci-
DigIN Slot0.1
343
fied by I/O reference B parameter (M3.3.4).
FALSE = OK
DigIN SlotA.3
405
TRUE = External fault
FALSE = External fault
DigIN Slot0.2
406
TRUE = OK
DigIN SlotA.6
414
Resets all active faults
DigIN Slot0.2
407
Must be on to set drive in Ready state
Drive may be ready but start is blocked as
DigIN Slot0.1 1041
long as interlock is on (Damper interlock).
DigIN Slot0.1 1042 As above.
Used for switching between ramps 1 and 2.
FALSE=Ramp 1 shape, Acceleration time 1
DigIN Slot0.1
408
and Deceleration time 1.
TRUE=Ramp 2 shape, Acceleration time 2
and Deceleration time 2.
FALSE = No action
TRUE = Uses the motor preheat DC-Current
DigIN Slot0.1 1044
in Stop state
Used when parameter M3.1.2.3 is set to 2.
FALSE = Fire Mode active
DigIN Slot0.2 1596
TRUE = No action
Binary selector for Preset frequencies (0-7).
DigIN SlotA.4
419
See page 37.
Binary selector for Preset frequencies (0-7).
DigIN SlotA.5
420
See page 37.
Binary selector for Preset frequencies (0-7).
DigIN Slot0.1
421
See page 37.
Rising edge starts Timer 1 programmed in
DigIN Slot0.1
447
Group 3.11: Timer functions parameter group
DigIN Slot0.1
448
See above
DigIN Slot0.1
449
See above
FALSE = No boost
DigIN Slot0.1 1047
TRUE = Boost
Honeywell