HVAC A
PPLICATION
3.5.5
Group 3.3: Control reference settings
Code
Parameter
M3.3.1
Minimum frequency
M3.3.2
Maximum frequency
I/O control reference A
M3.3.3
selection
I/O control reference B
M3.3.4
selection
Keypad Ctrl Refer-
M3.3.5
ence selection
M3.3.6
Keypad reference
M3.3.7
Keypad direction
Keypad reference
M3.3.8
copy
Fieldbus control refer-
M3.3.9
ence selection
Min
Max
Unit
0.00
M3.3.2
Hz
M3.3.1
320.00
Hz
1
8
1
8
1
8
0.00
M3.3.2
Hz
0
1
0
2
1
8
Default
ID
Minimum allowed frequency
0.00
101
reference
Maximum allowed frequency
60.00
102
reference
Selection of ref source when
control place is I/O A
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
6
117
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 reference
8 = Motor potentiometer
Selection of ref source when
control place is I/O B. See
above.
4
131
NOTE: I/O B control place
can only be forced active
with digital input (M3.5.1.5).
Selection of ref source when
control place is keypad:
1 = Preset Frequency 0
2 = Keypad
3 = Fieldbus
2
121
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 reference
8 = Motor potentiometer
The frequency reference can
0.00
184
be adjusted on the keypad
with this parameter.
Motor rotation when control
place is keypad
0
123
0 = Forward
1 = Reverse
Selects function for Run state
& Reference copy when
changing to Keypad control:
1
181
0 = Copy reference
1 = Copy ref & Run State
2 = No copying
Selection of ref source when
control place is Fieldbus:
1 = Preset frequency 0
2 = Keypad
3 = Fieldbus
3
122
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 reference
8 = Motor potentiometer
Honeywell
• 36
Description