Honeywell SmartVFD HVAC MR4 User Manual page 127

Variable frequency drives for constant and variable torque applications
Table of Contents

Advertisement

Honeywell
• 55
3.5.14.2
Setpoints
Code
Parameter
M3.12.2.1
Keypad setpoint 1
M3.12.2.2
Keypad setpoint 2
M3.12.2.3
Setpoint ramp time
Setpoint source 1
M3.12.2.4
selection
M3.12.2.5
Setpoint 1 minimum
M3.12.2.6
Setpoint 1 maximum
M3.12.2.7
Sleep frequency limit 1
M3.12.2.8
Sleep delay 1
M3.12.2.9
Wake-up level 1
M3.12.2.10
Setpoint 1 boost
Setpoint source 2
M3.12.2.11
selection
M3.12.2.12
Setpoint 2 minimum
Min
Max
Unit
Varies
Varies
Varies
Varies
Varies
Varies
0.00
300.0
s
0
16
-200.00
200.00
%
-200.00
200.00
%
0.00
320.00
Hz
0
3000
s
Varies
-2.0
2.0
x
0
16
-200.00
200.00
%
HVAC A
Default
ID
0
167
0
168
Defines the rising and falling
ramp times for setpoint
0.00
1068
changes. (Time to change
from minimum to maximum)
0 = Not used
1 = Keypad setpoint 1
2 = Keypad setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 = ProcessDataIn1
10 = ProcessDataIn2
11 = ProcessDataIn3
1
332
12 = ProcessDataIn4
13 = ProcessDataIn5
14 = ProcessDataIn6
15 = ProcessDataIn7
16 = ProcessDataIn8
AI's and ProcessDataIn are
handled as percent (0.00-
100.00%) and scaled accord-
ing to Setpoint minimum and
maximum.
NOTE:
two decimals.
Minimum value at analog sig-
0.00
1069
nal minimum.
Maximum value at analog
100.00
1070
signal maximum.
Drive goes to sleep mode
when the output frequency
0.00
1016
stays below this limit for a
time greater than that defined
by parameter Sleep delay.
The minimum amount of time
the frequency has to remain
0
1017
below the Sleep level before
the drive is stopped.
Defines the level for the PID
feedback value wake-up
0.0000
1018
supervision. Uses selected
process units.
The setpoint can be boosted
1.0
1071
with a digital input.
2
431
See par. M3.12.2.4
Minimum value at analog sig-
0.00
1073
nal minimum.
PPLICATION
Description
ProcessDataIn use