3.3
HVAC Application - Quick setup parameter group
The Quick Setup parameter group is a collection of parameters that are most commonly used
during installation and commissioning. They are collected in the first parameter group so that
they can be found fast and easily. They can, however, be also reached and edited in their ac-
tual parameter groups. Changing a parameter value in the Quick setup group also changes the
value of this parameter in its actual group.
Code
Parameter
M1.1
Motor nominal voltage
Motor nominal fre-
M1.2
quency
M1.3
Motor nominal speed
M1.4
Motor nominal current
M1.5
Motor Cos Phi
M1.6
Motor nominal power
M1.7
Motor current limit
M1.8
Minimum frequency
M1.9
Maximum frequency
I/O control reference A
M1.10
selection
M1.11
Preset frequency 1
M1.12
Preset frequency 2
M1.13
Acceleration time 1
M1.14
Deceleration time 1
M1.15
Remote control place
M1.16
Automatic reset
M1.17
PID Mini-Wizard
Min
Max
Unit
Varies
Varies
V
8.00
320.00
Hz
24
19200
rpm
Varies
Varies
A
0.30
1.00
0.00
Varies
kW
Varies
Varies
A
0.00
M3.3.1
Hz
M3.3.1
320.00
Hz
1
8
M3.3.1
300.00
Hz
M3.3.1
300.00
Hz
0.1
3000.0
s
0.1
3000.0
s
1
2
0
1
0
1
Default
ID
Find this value U n on the
Varies
110
rating plate of the motor.
See page 33.
Find this value f n on the rat-
60.00
111
ing plate of the motor. See
page 33.
Find this value n n on the rat-
1720
112
ing plate of the motor.
Find this value I n on the rat-
Varies
113
ing plate of the motor.
Find this value on the rating
0.80
120
plate of the motor
Find this value I n on the rat-
Varies
116
ing plate of the motor.
Maximum motor current
Varies
107
from AC drive
Minimum allowed frequency
Varies
101
reference
Maximum allowed frequency
60.00
102
reference
Selection of ref source when
7
117
control place is I/O A. See
page 36 for selections.
Select with digital input:
10.00
105
Preset frequency selection 0
(M3.5.1.16)
Select with digital input:
15.00
106
Preset frequency selection 1
(M3.5.1.17)
Time to accelerate from zero
20.0
103
to maximum frequency
Time to decelerate from min-
20.0
104
imum to zero frequency
Selection of remote control
place (start/stop)
1
172
1 = I/O
2 = Fieldbus
0 = Disabled
0
731
1 = Enabled
0 = Inactive
0
1803
1 = Activate
See chapter 1.2.