• 45
3.5.7.4
Expander slots D and E digital outputs
Code
Parameter
Application dynamic
output list
3.5.7.5
Analog outputs, Slot A (Basic)
Code
Parameter
M3.5.4.1.1
AO1 function
M3.5.4.1.2
AO1 filter time
M3.5.4.1.3
AO1 minimum
M3.5.4.1.4
AO1 minimum scale
M3.5.4.1.5
AO1 maximum scale
Min
Max
Table 30. Slot D/E digital outputs
Min
Max
0
19
0.00
300.00
0
1
Varies
Varies
Varies
Varies
Table 31. Basic I/O board analog output settings
Unit
Default
ID
Defaul
Unit
ID
t
2
10050
s
1.00
10051
0
10052
Varies
0.0
10053
Varies
0.0
10054
HVAC A
PPLICATION
Description
Shows only parameters for
existing outputs in slot D/E.
Selections as in Basic R01
Not visible if no digital output
exists in slot D/E.
Description
0=TEST 0% (Not used)
1=TEST 100%
2=Output freq (0 -fmax)
3=Freq reference (0-fmax)
4=Motor speed (0 - Motor
nominal speed)
5=Output current (0-I nMotor )
6=Motor torque (0-T nMotor )
7=Motor power (0-P nMotor )
8=Motor voltage (0-U nMotor )
9=DC link voltage (0-1000V)
10=PID1 output (0-100%)
11=PID2 output (0-100%)
12=ProcessDataIn1
13=ProcessDataIn2
14=ProcessDataIn3
15=ProcessDataIn4
16=ProcessDataIn5
17=ProcessDataIn6
18=ProcessDataIn7
19=ProcessDataIn8
NOTE:
For ProcessDataIn,
e.g. value 5000 = 50.00%
Filtering time of analog output
signal. See M3.5.2.2
0 = No filtering
0 = 0 mA / 0V
1 = 4 mA / 2V
Note the difference in analog
output scaling in parameter
M3.5.4.1.4.
Min scale in process unit
(depends on selection of AO1
function)
Max scale in process unit
(depends on selection of AO1
function)