Honeywell SmartVFD HVAC MR4 User Manual page 107

Variable frequency drives for constant and variable torque applications
Table of Contents

Advertisement

Honeywell
• 35
3.5.4
Group 3.2: Start/Stop setup
Code
Parameter
Remote control
M3.2.1
place
M3.2.2
Local/Remote
M3.2.3
Keypad stop button
M3.2.4
Start function
M3.2.5
Stop function
I/O A start/stop
M3.2.6
logic
I/O B start/stop
M3.2.7
logic
M3.2.8
AI1 start threshold
M3.2.9
Fieldbus start logic
Keypad Master
M3.2.10
Stop
Min
Max
Unit
0
1
0
1
0
1
0
1
0
1
0
3
0
3
3.00
100.00
%
0
1
0
1
Table 24. Start/Stop Setup menu
HVAC A
Default
ID
Description
Selection of remote control
place (start/stop). Can be
used to change back to
remote control from PC
0
172
e.g. in case of a broken
panel.
0=I/O control
1=Fieldbus control
Switch between local and
remote control places
0
211
0=Remote
1=Local
0=Stop button always
enabled (Yes)
0
114
1=Limited function of Stop
button (No)
0=Ramping
0
505
1=Flying start
0=Coasting
0
506
1=Ramping
CtrlSgn 1
0=Start fwd
1=Start fwd pulse(3-wire)
2=Start fwd pulse
3=AI1 threshold
0
300
CrtlSgn 2
0=Start fwd
1=Stop pulse (3-wire)
2=Start fwd pulse
3=AI1 threshold
0
363
See above.
If M3.2.6 (I/O Start/Stop
Logic) is set to value 3 (AI1
threshold) the motor will
start at the level set with
5.00
185
parameter this parameter
and stop at the same -2%
AI1 can also be used as
frequency reference at the
same time.
0=Rising edge required
1
889
1=State
0=Disable
1
1806
1=Enable
PPLICATION