Honeywell SmartVFD HVAC MR4 User Manual page 123

Variable frequency drives for constant and variable torque applications
Table of Contents

Advertisement

Honeywell
• 51
3.5.12
Group 3.10: Automatic reset
Code
Parameter
M3.10.1
Automatic reset
M3.10.2
Restart function
M3.10.3
Wait time
M3.10.4
Trial time
M3.10.5
Number of trials
Autoreset:
M3.10.6
Undervoltage
Autoreset:
M3.10.7
Overvoltage
Autoreset:
M3.10.8
Overcurrent
M3.10.9
Autoreset: AI low
Autoreset: Unit over-
M3.10.10
temperature
Autoreset: Motor over-
M3.10.11
temperature
Autoreset:
M3.10.12
External fault
Autoreset:
M3.10.13
Underload fault
Min
Max
Unit
0
1
0
1
0,10
10000,0
s
0,00
10000,0
s
1
10
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Table 37. Autoreset settings
Default
ID
0 = Disabled
0
731
1 = Enabled
The start mode for Automatic
reset is selected with this
1
719
parameter:
0 = Flying start
1 = According to par. M3.2.4
Wait time before the first
0,50
717
reset is executed.
When the trial time has
elapsed, and the fault is still
60,00
718
active, the drive will trip to
fault.
NOTE: Total number of trials
4
759
(irrespective of fault type)
Autoreset permitted?
1
720
0 = No
1 = Yes
Autoreset permitted?
1
721
0 = No
1 = Yes
Autoreset permitted?
1
722
0 = No
1 = Yes
Autoreset permitted?
1
723
0 = No
1 = Yes
Autoreset permitted?
1
724
0 = No
1 = Yes
Autoreset permitted?
1
725
0 = No
1 = Yes
Autoreset permitted?
0
726
0 = No
1 = Yes
Autoreset permitted?
0
738
0 = No
1 = Yes
HVAC A
PPLICATION
Description

Hide quick links:

Advertisement

Table of Contents