General Information
The GSMHS is designed to deliver alarms via the GSM network to an AlarmNet central
station when it is registered with a valid AlarmNet account.
The GSMHS module requires an AlarmNet–i account. For new installations, please obtain the
account information from the central station prior to programming this module. For replacement
installations, the AlarmNet-i account is created automatically when the module is registered (based
on the existing account).
You can program a GSMHS by one of the following methods:
Through the AlarmNet Direct website
Through use of a 7720P Programming Tool
Through a programming mode in the control panel on panels that support this option
(e.g., VISTA-128BP and FBP)
UL
Only ECP and Zone Trigger modes have been evaluated by UL.
Programming the Control Panel to work with the GSMHS
For Residential and Commercial control panels, there are certain programming field settings
that must be adhered to for using the GSMHS. (For programming information, please refer
to the appropriate control panel guides.) Ensure the following programming fields are set as
follows:
RESIDENTIAL / COMMERCIAL Control Panels (Such as the VISTA-10P, 15P, and 20P series.)
Programming Field
29 Menu Mode for IP/GSM Enable
54 Dynamic Signaling Delay
55 Dynamic Signaling Priority
COMMERCIAL Control Panels (Such as the VISTA-128/250 series.)
Programming Field
56 Dynamic Signaling Delay
57 Dynamic Signaling Priority
58 Comm Central Station #1
59 Comm Central Station #2
#93 Menu Mode
Category Enable
Category Enable
Programming the GSMHS
Setting
1 (Enable LRR.)
0 (Dialer and LRR reports go out at the same time.)
0 (Primary dialer reports first.)
Setting
00 (Dialer and LRR reports go out at the same time.)
1 (Communicator, as first reporting.)
111111 (All events will be reported to the primary Central
Station.)
000000 (If Central Station #2 is not used.)
111111 (If Central Station #2 is used.)
Zone programming – set Zone 803 for Type 05.
Device programming – set Address 03 for Type 06 (LRR).