Programming for UL864 Compliance

The 7847i-E provides a programmable supervision features that allows the system to meet the UL864
Commercial Fire requirements. These requirements are in the following table.
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options
must be limited to specific values or not used at all as indicated below.
Program feature or option
Supervision
Old Alarm Time
IP Fault Time
Flt Rel ON
ECP MODE PROGRAMMING
Zn6 Trigger Type
Zn7 Trigger Type
Delay Zn6
Delay Zn7
ZONE TRIGGER MODE
PROGRAMMING
Zn1 Trigger Type
to
Zn8 Trigger Type
Delay Zn1
to
Delay Zn8
1-4
Possible settings
24 Hours
• CN 90 Sec
• 1 Hour
• 75 Sec
• 6 Min
• None
• 3 Min
• 30 Day
• 90 Sec
•10 Minutes
• 15 Minutes
• 30 Minutes
• 1 Hour
• 2 Hours
• 4 Hours
• 8 Hours
• 12 Hours
• 24 Hours
[00-99]
[Y], [N]
• (V+)
• (V–)
• (EOLR)
[01-15]
[00] = no delay
• (EOLR)
• (V+)
• (V–)
[01-15]
[00] = no delay
Settings permitted in UL 864
Must be set to:
• 3 minutes for UL Comm Fire/Burg or
ULC Active Channel Security.
security
• 4 Hours
Must be 10 minutes.
• 8 Hours
• 12 Hours
• 24 Hours
Must be one (01) minute.
Must be set to "Y."
V+ must be set as inverted and V- as
non-inverted
Must be 00
V+ must be set as inverted and V- as
non-inverted
Must be 00
24hrs for ULC Passive channel