Wiring For Module Fault Relay; Power Connections And Options; Powering The Communication Module - Honeywell AlarmNet GSMHS Installation And Setup Manual

High security gsm cellular communicator
Table of Contents

Advertisement

Wiring for Module Fault Relay

You may wire and program the module's fault output trigger for fail-safe mode (see the
question "FLT REL ON Y/N").
To sense a module fault at the control panel, make connections as shown in Figure 2-6,
including the proper EOL resistor required by the control.
A 24 hour supervisory zone must be assigned on the control panel, with the GSMHS's fault relay wired to
UL
that zone.
Figure 2-6. Wiring the GSMHS Fault Relay to a Control Panel Zone for Normally Closed Fault

Power Connections and Options

Powering the Communication Module

Primary power for the GSMHS is provided by the AC plug-in transformer. For ECP
communication, you must also connect the +12VDC AUX voltage output of the control panel
(9.6V-13.8V typical) (see Figure 2-7).
In all installations, TB1-4 GND must be connected to ground (AUX –) on the control panel.
NOTE:
12V AUX
GND
ZONE IN (+)
CONTROL PANEL
12V AUX
-
AUX
CONTROL PANEL
Figure 2-7. Powering the GSMHS
When calculating the total load on the auxiliary power output of the control panel, budget 10mA
for the GSMHS when using ECP mode.
TRANSFORMER
TB1
1
2
3
4
2K EOL
RESISTOR
11
COMMUNICATIONS
MODULE
TRANSFORMER
TB1
1
2
3
4
COMMUNICATIONS
MODULE
Section 2: Mounting and Wiring
AC INPUT 1
AC INPUT 2
ECP (+) VOLTAGE INPUT
GND
RAD FLT
BATTERY
J1
AC INPUT 1
AC INPUT 2
ECP (+) VOLTAGE INPUT
GND
BATTERY
J1
2-5